| Flow Sensors (with pulse output) |
Max. Frequency
Min. Pulse Length
Max. Voltage
Max. Cable Length |
12 Hz
40 ms
3 V
49.2 ft |
|
| Temperature Sensors |
Max. Cable Length
Max. Sensor Current |
8.2 ft at 31 gauge cable area
16.4 ft at 24 gauge cable area
24.6 ft at 21 gauge cable area
49.2 ft at 15 gauge cable area
4 mA (RMS) for Pt 100 |
|
| Power Supply |
Battery
|
3V - 2.2 Ah
10 Year Design Life
|
|
|
| Temperature |
Range
Difference
|
32 - 374° F
2 - 100 K |
|
| Data Output |
M-Buss (EN1434-3)
|
Via OPTO-interface (EN60870-5) and via bus connection (terminal) |
|
| Pulse Outputs (Open Collector) |
Pulse Length
Max. Voltage
Max. Current |
250 ms
30 V
20 mA |
|
| Ambient Temperature |
Operation
Storage/Transport
|
+41° F to +131° F
-4° F to +158° F |
|
| Pulse Inputs |
Max. Frequency
Min. Pulse Length
Max. Voltage |
12 Hz
40 ms
3 V |
|
| Protection Class IP54 |
| Environmental class C according to EN1434 |
. |
|
| Alarm Output (Open Collector) |
| Pulse Length
|
250 ms
|
|